20/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
8 Panel design
8.1 Function
The circuit-breaker panel is the basic panel type of the 8DB10. The circuit-breaker panel can
fulfil the function "incoming feeder" or "outgoing feeder". It can carry or switch all rated
busbar and feeder currents as well as the short-circuit currents quoted on the respective rating
plates.
8.2 Subframe
Support for switchpanel poles and panel front
Forms the cable compartment
•Subframe versions
- Standard: Switchgear height 2350 mm
- Higher version: Switchgear height 2570 mm
8.3 Low-voltage compartment
For accommodation of protection, control, measuring and metering equipment
With plug-in cables of the circuit-breaker and three-position disconnector operating
mechanisms on top-hat rail for incoming and outgoing cables (e.g. bus wires)
Devices can be optionally mounted in the door or on top-hat rail inside the low-voltage
compartment
Height of low-voltage compartment, optionally 850 mm (standard) or 1200 mm
8.4 Switchpanel pole
Poles arranged one behind the other.
One switchpanel pole consists of a vertically arranged housing with a vacuum interrupter
inside.
Over the switchpanel pole, there are the disconnector housings for busbar system 1 and 2,
and above these the respective busbar housings in horizontal arrangement.