39.3 Opening
Fig. 196: Opening the busbar earthing switch (basic scheme)
Push the control gate to the left.
The position indicator changes to faulty position.
Hold the operating lever in horizontal position.
Insert the operating lever in the actuating opening as far as it will go.
Observe the position of the operating spindle.
Turn the operating lever 180° counter-clockwise.
Remove the operating lever.
The control gate is in its initial position again.
The position indicator changes from faulty position to OPEN position.
Optionally: Padlock the control gate.
The busbar earthing switch is open.
Fig. 197: Position indicator at the busbar earthing switch (basic scheme)
ATTENTION
The control gate can only be moved to a position that is permissible at this moment.
Observe the position indicator at the busbar earthing switch.
ATTENTION
Once you have started a switching operation, you must complete it totally; turning back is
blocked. The operating lever cannot be removed at intermediate positions.
Do not remove the operating lever at intermediate positions.