Operation
146/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Operation
35 Control elements and indicators
Overview
DANGER
The internal arc classification of the switchgear according to IEC 62271-200 has only been
proved by tests for the switchgear sides with internal arc classification and with closed
high-voltage compartments.
Determine the IAC classification of the switchgear by means of the data on the rating plate
(see page 48, "Rating plates").
Regulations for access to switchgear areas without internal arc classification according to
IEC 62271-200 must be defined by the entrepreneur or the switchgear operator.
Fig. 164: Switchgear front
Manometers of the SF
6
gas compartments for busbars L1, L2, L3 of
busbar system 1
Manometers of the SF
6
gas compartments for busbars L1, L2, L3 of
busbar system 2
Gas filling valve
"ON" pushbutton (mechanical), sealable and lockable by the customer
"OFF" pushbutton (mechanical), sealable and lockable by the customer
Locking device
Sockets for voltage detecting system
Counter for operating cycles
Position indicator for circuit-breaker "CLOSED"/"OPEN"
"Closing spring charged / not charged" indicator
Opening for hand crank for charging the circuit-breaker closing spring
Selector gate for busbar system
Control and indication board for three-position disconnector operating
mechanism
Gas filling valve
Manometer for three-position disconnector housing in busbar system 1
Manometer for circuit-breaker housing
Manometer for three-position disconnector housing in busbar system 2
Low-voltage compartment