864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 97/214
Installation
26.1 Installation of voltage transformers type 4MT3 on the busbar
Isolate and earth the busbar.
Verify safe isolation from supply.
For first installation: Remove protective cap.
If available: Disassemble surge-proof caps of the outside-cone bushing.
Clean the silicone adapter of the voltage transformer and the outside-cone bushing
carefully. Use a cleaning agent without solvents and a lint-free cloth.
Grease the silicone adapter of the voltage transformer and the outside-cone bushing of
the voltage transformer mounting plate uniformly with mounting paste for cable sets.
Fig. 100: 4MT3 busbar voltage transformer
(shown without cover)
4MT3 voltage transformer
Low-voltage plug connector
Adapter plate
Voltage transformer
mounting plate
Busbar housing
Distance sleeves
Outside-cone bushing
Hole with setnut for press-out bolt