EasyManua.ls Logo

Siemens 8DB10 - Installation of Voltage Transformers Type 4 MT3 on the Busbar

Siemens 8DB10
214 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 97/214
Installation
26.1 Installation of voltage transformers type 4MT3 on the busbar
➭ Isolate and earth the busbar.
➭ Verify safe isolation from supply.
➭ For first installation: Remove protective cap.
If available: Disassemble surge-proof caps of the outside-cone bushing.
➭ Clean the silicone adapter of the voltage transformer and the outside-cone bushing
carefully. Use a cleaning agent without solvents and a lint-free cloth.
➭ Grease the silicone adapter of the voltage transformer and the outside-cone bushing of
the voltage transformer mounting plate uniformly with mounting paste for cable sets.
Fig. 100: 4MT3 busbar voltage transformer
(shown without cover)
①
4MT3 voltage transformer
②
Low-voltage plug connector
③
Adapter plate
④
Voltage transformer
mounting plate
⑤
Busbar housing
⑥
Distance sleeves
⑦
Outside-cone bushing
⑧
Hole with setnut for press-out bolt

Table of Contents