Installation
64/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
21.3 Checking the SF
6
gas pressure
To exclude any gas losses during transportation in the gas compartments filled at the factory,
check the gas pressure indicators on the panels.
Check the gas pressure in the compartments pre-filled at the factory on the associated gas
pressure indicators. The values must not drop below the temperature-dependent limit
values.
If the filling pressure is too low: Do not assemble the part of the switchgear concerned and
inform the regional Siemens representative.
Fig. 52: Gas pressure manometers at the panel
Gas pressure manometers for the busbar
compartments in system 1
Gas pressure manometers for the busbar
compartments in system 2
Gas pressure manometer for three-
position disconnector housing in
system 2
Gas pressure manometer for circuit-
breaker housing
Gas pressure manometer for three-
position disconnector housing in
system 1
Critical gas pressure (signaling contact)
Minimum permissible gas pressure
(signaling contact)
Actual gas pressure
Maximum permissible gas pressure
(signaling contact)
Fig. 53: Gas pressure manometer for the circuit-
breaker housing at the panel
DANGER
Operation with incorrect SF
6
gas pressure can destroy parts of the switchgear.
Do not install or put the switchgear into operation with incorrect SF
6
gas pressures.