27.3 Removal of voltage transformers type 4MT7 from the cable feeder
Isolate and earth the cable feeder.
Verify safe isolation from supply.
Remove the voltage transformer. To do this, remove the 4 bolts of the fixing brackets at
the panel connection cover, bolt size M10.
Fig. 120: Removing the voltage transformer
Fig. 119: 4MT7 voltage transformer
Panel connection housing
Inside-cone bushing for primary
terminal of transformer
Primary terminal at the voltage
transformer
Silicone adapter
Fixing bracket (fixed at the voltage
transformer housing)
4MT7 voltage transformer
Low-voltage plug connection
Inside-cone bushing for cable
Panel connection cover
ATTENTION
Risk of injury! While being removed from the bushing, the voltage transformer can detach
suddenly.
Remove the voltage transformer uniformly downwards.
Do not use excessive force.