EasyManua.ls Logo

Siemens 8DB10 - Circuit-breaker operation

Siemens 8DB10
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
148/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
36 Circuit-breaker operation
Circuit-breaker
control board
36.1 Closing the circuit-breaker manually
Preconditions "Feeder earthed" locking device is open
Closing spring is charged
Operate the ON pushbutton in the circuit-breaker control board.
The position indicator changes to "I" position. The circuit-breaker is closed.
36.2 Opening the circuit-breaker manually
If the control voltage fails, the circuit-breaker can only be opened mechanically by hand.
Preconditions "Feeder earthed" locking device is open
Operate the OFF pushbutton in the circuit-breaker control board.
The circuit-breaker is open.
ATTENTION
Operating the circuit-breaker locking device in the OPEN or CLOSED positions can damage
the switchgear.
Operate the circuit-breaker locking device only in the EARTHED position, and padlock it.
Fig. 170: Circuit-breaker control board
ON pushbutton
OFF pushbutton
"Feeder earthed“ locking device
Operations counter
Position indicator for
circuit-breaker
"Closing spring charged / not
charged“ indicator
Opening to charge
the closing spring manuallly
NOTE
OFF signals ineffective
If the feeder is earthed through the three-position disconnector and the circuit-breaker,
all electrical OFF signals are ineffective.
DANGER
If the "feeder earthed" locking device is padlocked, the circuit-breaker cannot be opened,
neither electrically nor mechanically.
Fit the padlock only if the feeder is earthed.