864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 135/214
Installation
32 Installation of rear walls of switchgear
Fasten the fixing cross members at the retainers and the busbar housings using 2 bolts
M8 x 30 each. Tightening torque: 20 Nm.
ATTENTION
If higher busbar housings with disconnectable feeders to the top are mounted on intermediate
and end panels:
Turn the fixing cross member for installation by 180°.
Fig. 148: Mounting fixing cross members on busbar housings
Fixing cross members for right and left end panels
The fixing cross member for intermediate panels is identical with the fixing cross member for end
panels. However, the fixing cross member is turned by 180° if a higher busbar housing with a
disconnectable feeder to the top was mounted.

Table of Contents