Description
22/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
9 Circuit-breaker
9.1 Design
The vacuum circuit-breaker is an integral part of the switchgear panel and consists of the
following components:
Operating mechanism with stored-energy spring mechanism and control elements (3AH49)
Operating linkage for contact operation
3 switchpanel poles with vacuum interrupters
Mechanical interlocking The circuit-breaker and the three-position disconnector are mechanically interlocked against
each other. During manual operation, the mechanical interlock prevents the circuit-breaker
from being closed as long as the three-position disconnector is not in a defined end position
(CLOSED/OPEN/EARTHED). Furthermore, the mechanical interlock prevents the three-position
disconnector from being operated while the circuit-breaker is closed.
Vacuum interrupters
Fig. 5: Sectional view of
a vacuum interrupter
Moving contact
Metal bellows
Fixed contact