864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 207/214
Servicing
44.7 Lubricants
44.8 Switchgear extension and replacement of panels and components
For switchgear extension and replacement of components, please contact the regional
Siemens representative.
Information required for spare part orders of single components and devices:
• Type and serial number of the switchgear and the circuit-breaker (see rating plates)
• Precise designation of the device or component, if applicable on the basis of the information
and illustrations in the associated instructions, a drawing, sketch or circuit diagram
44.9 Spare parts
Due to the fact that all parts of this switchgear type have been optimized to last the normal
service life, it is not possible to recommend particular spare parts.
Designation Manufacturer Application Comment
Polylub GLY 801 Siemens Current-carrying fixed-mounted
connections (current conductors and
earthing bars, connections),
flanges with toroidal sealing rings
No greasing effect; used as
mounting aid for toroidal sealing
rings; mounting paste for flanges
Barrierta GTE 403 Klüber Contact blades and contacts of
the three-position disconnector
Observe the designation "GTE 403"
in order to avoid mistakes with
other Barrierta products
Longtherm 2+ Molykote Bearings of the operating linkage Not suitable for greasing points
on the circuit-breaker operating