Installation
104/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
26.3 Installation of voltage transformers type 4MT7 at the cable feeder
Isolate and earth the cable feeder.
Verify safe isolation from supply.
For first installation of the voltage transformer, mount the threaded rods M10 with low-
design nuts (flat nuts) according to DIN 4035 on the panel connection cover (installation
instruction enclosed with the supplementary equipment).
Fig. 108: 4MT7 voltage transformer
Panel connection housing
Inside-cone bushing for primary terminal of transformer
Primary terminal at the voltage transformer
Silicone adapter
Fixing bracket (fastened to the voltage transformer housing)
4MT7 voltage transformer
Low-voltage plug connector
Inside-cone bushing for cable
Panel connection cover
Fig. 109: Mounting the threaded rods
Panel connection housing
Panel connection cover
M10 nuts acc. to DIN 4035
Threaded rods M10
Note: Nuts
and threaded
rods
are included in the
supplementary equipment