864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 105/214
Installation
For first installation: Remove protective cap.
If available: Disassemble surge-proof dummy plugs of the inside-cone bushings.
To do this, undo the two sets of three M8 bolts.
Fig. 110: Removing surge-proof dummy plugs
Clean the silicone adapter and the inside-cone cast-resin socket carefully. Use a cleaning
agent without solvents and a lint-free cloth.
Grease the silicone adapter and the inside-cone cast-resin socket uniformly with mounting
paste for cables sets.
Fig. 111: Greasing the silicone adapter
Fig. 112: Greasing the inside-cone
cast-resin socket
Inside-cone bushing for plug-in cable connection
Inside-cone bushing for primary terminal of transformer
DANGER
Risk of injury! The voltage transformer type 4MT7 has a weight of approx. 35 kg.
Secure the voltage transformer from below against falling down.
If necessary, transport the voltage transformer with several persons or with suitable aids.
If necessary, support the voltage transformer with a suitable facility.