864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 159/214
Operation
To push the control gate from the right or left position to the center position again:
Remove the plug (according to the position of the control gate) and push the solenoid back
with the screwdriver.
Push the control gate to the center position.
After work completion, pull the screwdriver out and refit the stopper.
The solenoid is released again, blocking further movements.
Fig. 184: Pushing the control gate to the center position
37.8 Emergency operation of the three-position disconnector
If the motor voltage of the three-position disconnector with motor operating mechanism fails
and the three-position disconnector is in no defined end position, the three-position
disconnector must be operated manually.
Adapter for
emergency operation
Push emergency operation adapter on operating lever for three-position disconnector.
Fig. 185: Marking (long slot) on operating lever with pushed-on adapter
ATTENTION
If the operating lever with pushed-on adapter is incorrectly used, the indicator or even the
operating mechanism of the three-position disconnector can be damaged.
The operating lever with pushed-on adapter is not aligned according to the noses of the
standard operating lever, but according to the adapter slots.