EasyManua.ls Logo

Siemens 8DB10 - Switching Operations in Top-Mounted Bus Sectionalizer, System 1

Siemens 8DB10
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
194/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
42.4 Switching operations in top-mounted bus sectionalizer, system 1
Coupling busbar sections (system 1)
1
Initial situation
2
Push the left-hand control gate to the left.
3
Switch the three-position disconnector to CLOSED position (insert
the operating lever for the DISCONNECTING function and turn 180°
clockwise).
4
Remove the operating lever for the DISCONNECTING function.
The left-hand control gate returns to its initial position.
5
Push the right-hand control gate to the left.
6
Switch the three-position disconnector to CLOSED position (insert the
operating lever for the DISCONNECTING function and turn 180°
clockwise).
7
Remove the operating lever for the DISCONNECTING function.
The right-hand control gate returns to its initial position.

Table of Contents