EasyManua.ls Logo

Siemens 8DB10 - Removal of Voltage Transformers Type 4 MU4 from the Busbar

Siemens 8DB10
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 109/214
Installation
Clean the silicone adapter and the outside-cone bushing carefully using a cleaning agent
without solvents and a lint-free cloth.
Protect the connection socket of the voltage transformer against damages and pollution
using a suitable cover.
For voltage tests: Close the outside-cone bushing at the busbar housing with a surge-proof
cap and protect it against damages and pollution.
27.2 Removal of voltage transformers type 4MU4 from the busbar
Isolate and earth the busbar.
Verify safe isolation from supply.
Remove the low-voltage plug connection.
Remove the 4 fixing bolts M8x35 of the fixing brackets at the voltage transformer
mounting plate.
Fig. 116: Removing the fixing bolts at the voltage transformer mounting plate
Lift the voltage transformer at the upper crane eyes using a suitable rod (e.g. steel rod).
NOTE
If you remove the voltage transformer, the silicone adapter may fall out of the voltage
transformer.
Keep the silicone adapter carefully for later use.