864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 205/214
Servicing
44.5 Maintenance of the vacuum circuit-breaker operating mechanism
Under normal operating conditions the fixed-mounted circuit-breaker switchgear 8DB10 and
the 3AH49 circuit-breaker are maintenance-free.
After 10,000 operating cycles or depending on the respective operating conditions (e. g.
dusty environment, frequent condensation, etc.) we recommend to clean the external parts
and, if necessary, to renew the anti-corrosion protection greasing. To do this, you may only
use the materials specified hereafter on the individual functional parts of the circuit-breaker.
Fig. 215: Greasing plan for 3AH49 operating mechanism
Isoflex Topas L 32 Shell Tellus Oil 32
Curve contour
Bearing for deflection lever
Closing latch
Auxiliary switch
Deflection of auxiliary switch
Bearing of operating shaft
Guide of opening spring
Opening spring
Deflecton of auxiliary switch
Opening latch
Curve for opening latch
End stop
Crank pin for pushbutton operation