Operation
178/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Indications VOIS, VOIS R+,
CAPDIS -S1+/-S2+
Fig. 210: CAPDIS-S2+: Cover closed
Fig. 211: CAPDIS-S2+: Cover opened
"Test" button
Cover
LC display
Duct for signaling cables CAPDIS-M
Test socket L2
Earth socket
Test socket L3
Test socket L1
Short instructions
Indicatio
n
VOIS+, VOIS R+ CAPDIS-S1+ CAPDIS-S2+
L1 L2 L3 L1 L2 L3 L1 L2 L3
A0 Operating voltage not present (CAPDIS-S2+)
A1 Operating voltage present
A2 Operating voltage not present
Auxiliary power not present (CAPDIS-S2+)
A3 Failure in phase L1, operating voltage at L2 and
L3 (for CAPDIS-Sx+ also earth-fault indication)
A4 Voltage (not operating voltage) present
A5 Indication: "Test" passed (lights up shortly)
A6 Indication: "Test" not passed (lights up shortly)
A7 Overvoltage present (lights up permanently)
A8 Indication: "ERROR" e.g., in case of missing
auxiliary voltage