864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 179/214
Operation
41.3 Indications WEGA 1.2, WEGA 2.2
Indications WEGA 1.2,
WEGA 2.2
DANGER
High voltage! Danger! Verify safe isolation from supply without any doubt!
Possible sources of failure:
- Defective voltage indicator (or device for function testing of the coupling section)
- Maloperation of the voltage indicator (or device for function testing of the coupling
section)
Use only voltage indicators or devices according to EN 61 243-5 / IEC 61 243-5 / VDE 0682-
415 to test the function of the coupling section. (The interface conditions have not
changed as against the old standard VDE 0681 Part 7; the corresponding indicators can still
be used.)
Fig. 212: Operating elements WEGA 1.2/2.2
LC display (illuminated for WEGA 2.2)
Test socket L3
Test socket L1
Earth socket
Test socket L2
"Display Test" button
Indication WEGA 1.2 WEGA 2.2
L1 L2 L3 L1 L2 L3
A0 For WEGA 2.2: Operating voltage not present,
auxiliary power present, LCD illuminated
A1 Operating voltage present
•For WEGA 2.2:
Auxiliary power present, LCD illuminated
A2 Operating voltage not present
•For WEGA 2.2:
Auxiliary power not present, LCD not illuminated
A3 Failure in phase L1, operating voltage at L2 and L3
•For WEGA 2.2:
Auxiliary power present, LCD illuminated
A4 Voltage present, current monitoring of
coupling section below limit value
For WEGA 2.2: Auxiliary power present, LCD illuminated
A5 Indication: "Display Test" passed
For WEGA 2.2: Auxiliary power present, LCD illuminated
A6 For WEGA 2.2:
LCD for missing auxiliary voltage is not illuminated