Servicing
206/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Permissible lubricants:
Renew the anti-corrosion protection greasing.
Operate the circuit-breaker several times mechanically by hand for test.
44.6 Cleaning agents and cleaning aids
For bearings, sliding surfaces:
Isoflex Topas L 32
Klüber - Lubrication KG
Geisenhauer Str. 7
Postfach 70 10 47
D-81310 München
For bearings that are inaccessible for
grease, and bearings of the auxiliary
switch S1:
Tellus Oil 32
Shell Direct GmbH
Suhrenkamp 71
D-22335 Hamburg
ATTENTION
Parts of the switchgear that cannot be dismantled may be damaged if they come into contact
with cleaning agents.
➭Do not wash joints and bearings which cannot be dismantled with a cleaning agent.
DANGER
For protection of personnel and environment:
Read the instructions for use of cleaning agents carefully.
Observe the warnings (e.g. inflammable!, corrosive!, etc.)
Cleaning agents HAKU 1025-920 Contains carbon hydrogen!
Household cleaner For cleaning electrostatically stressed insulation (e.g. epoxy
resin)
Cleaning aids Lint-free cleaning paper For applying and cleaning liquid cleaning agent (single use)
Brush
Cleaning rag
Vacuum cleaner

Table of Contents