Description
24/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
10 Disconnector and three-position disconnector
Function of three-position
disconnector
Busbar system 1 is equipped with a the three-position disconnector which combines the
functions of a disconnector and an earthing switch. It is designed for no-load operation only.
Function of disconnector A disconnector is installed in busbar system 2. It is designed for no-load operation only.
The disconnector has a work-in-progress earthing contact for maintenance work,
which cannot be operated during normal operation.
ATTENTION
The work-in-progress earthing contact of the disconnector in busbar system 2 is designed for
maintenance work at the three-position disconnector in busbar system 1 in de-energized
condition only.
Before switching to the work-in-progress earthing contact, always contact your regional
Siemens representative.
Fig. 7: 8DB three-position disconnector for busbar
system 1 and three-position disconnector
for busbar system 2
Fixed contact of busbar,
busbar system 1
Fixed contact of busbar,
busbar system 2
Work-in-progress earthing contact
for system 2
Moving contact for
system 2 in OPEN position
Bushing
Fixed contact for
READY-TO-EARTH, system 1
Moving contact for
system 1 in OPEN position

Table of Contents