42 Overview of switching operations
42.1 Switching operations in the circuit-breaker panel
Connecting the feeder with busbar system 1
1
Initial situation
2
➭ Push the selector gate to the left.
3
➭ Push the left-hand control gate to the left.
4
➭ Switch the three-position disconnector to CLOSED position 
(insert the operating lever for the DISCONNECTING function and turn 
180° clockwise).