864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 57/214
Installation
Foundation Please observe the following items when preparing the foundation:
Dimensions of the floor opening and the fixing points of the switchgear frame
(see page 53, "Constructional data of the foundation").
Determine level differences between the installation surfaces of the panels using
a measuring sheet, and compensate them with shims (0.5 - 1.0 mm).
Fig. 50: Measuring sheet for the foundation
The measuring sheet for the foundation shows: Evenness/straightness tolerance according to
DIN 4366: 1 mm for 1 m length, 2 mm for the total length.
Regulations and
standards referred to
foundation and
switchgear room
The switchgear can be used as indoor installation according to IEC 61 936 (Power Installations
exceeding 1 kV AC) and VDE 0101
outside lockable electrical service locations at places which are not accessible to the public.
Enclosures of switchgear can only be removed with tools
in lockable electrical service locations. A lockable electrical service location is a place
outdoors or indoors that is reserved exclusively for housing electrical equipment and
which is kept under lock and key. Access is restricted to authorized personnel and persons
who have been properly instructed in electrical engineering
For more information, see page 46, "Standards, specifications, guidelines".
19.3 Transport units
Dimensions
Panel widths Transport dimensions Transport weight with
packing
1)
Transport weight
without packing
1)
mm Width x Height x Depth
mm x mm x mm
approx. kg approx. kg
Transport inside Germany or to European countries
1 x 600 1816 x 2550 x 3124 1300 1200
2 x 600 1816 x 2550 x 3124 2600 2400
3 x 600 2416 x 2550 x 3124 3900 3600
Transport to overseas
1 x 600 1840 x 2850 x 3124 1300 1200
2 x 600 1840 x 2850 x 3124 2600 2400
3 x 600 2440 x 2850 x 3124 3900 3600
1)
Average values depending on the degree to which panels are equipped