110/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Remove the voltage transformer slowly upwards by means of the steel rods.
Lower the transformer so that it does not lie on the primary terminal, and protect it against
damages and pollution using a suitable cover.
For voltage tests: Close the inside-cone bushing at the panel with
a surge-proof dummy plug size 2.
To do this, remove the 3 bolts M8x25. Store these bolts carefully. Fit the dummy plug and
bolt together with 3 bolts M8.
Fig. 117: Removing bolts M8x25
ATTENTION
Risk of injury! While being removed from the bushing, the voltage transformer can detach
suddenly.
Remove the voltage transformer upwards as uniformly as possible.
Do not use excessive force.
ATTENTION
Risk of injury! The voltage transformer type 4MU4 has a weight of approx. 60 kg.
Secure the voltage transformer against falling down.
If necessary, transport the voltage transformer with several persons or with suitable aids
(e.g. a supporting rod).
Fig. 118: Inserting the dummy plug
M8 bolts