Operation
160/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Fig. 186: Marking (short slot) on operating lever with pushed-on adapter
The noses of the operating lever are not significant for evaluating the position of the
operating mechanism.
End positions of the three-position switch while switching with the operating lever
with pushed-on adapter
Insert the operating lever with pushed-on adapter in such a way that the inner slot of
the adapter fits on the pin of the operating shaft.
Fig. 187: Inserting the operating lever with pushed-on adapter
ATTENTION
The operating lever does not have a stop. Switching beyond the end position of
the three-position switch with the operating lever with pushed-on adapter will damage
the three-position switch.
Do always observe the markings on the adapter of the operating lever.