Installation
106/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Lower the primary terminal of the voltage transformer slowly onto
the panel connection housing.
To let excess air out of the plug connection while mounting the voltage transformer,
fit a nylon thread or a cable strap into the inside cone of the panel connection cover.
Insert the primary terminal of the voltage transformer slowly into the inside cone of the
panel connection cover, pulling the cable strap out at the same time.
Fit plain washers on the threaded rods of the fixing bracket stecken. Bolt the voltage
transformer uniformly together with the panel connection cover using the M10 nuts.
Tightening torque: 30 Nm.
Fig. 114: Bolting the voltage transformer together
Connect the low-voltage plug connector to the voltage transformer.
Fig. 113: Mounting the voltage transformer
Cable strap