Installation
112/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Remove the voltage transformer slowly downwards.
Lower the voltage transformer so that it does not lie on the primary terminal, and protect it
against damages and pollution using a suitable cover.
For voltage tests: Close the inside-cone bushings at the switchpanel pole with surge-proof
dummy plugs size 2 (3), and bolt tight using 3 bolts M8 each.
Fig. 121: Mounting surge-proof dummy plugs
ATTENTION
Risk of injury! The voltage transformer type 4MT7 has a weight of approx. 35 kg.
Secure the voltage transformer against falling down.
If necessary, transport the voltage transformer with several persons or with suitable aids.
If necessary, support the voltage transformer with a suitable facility.