Operation
156/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Pre-select busbar system for switching operation.
Selector gate to the left: Busbar system 1. Selector gate to the right: Busbar system 2 .
Push the left-hand control gate to the right.
The opening for the READY-TO-EARTH function is free.
Switch the three-position disconnector to READY-TO-EARTH position (insert the operating
lever for the READY-TO-EARTH function and turn 180° clockwise).
The earthing switch is closed.
The position indicator changes to READY-TO-EARTH position.
Remove the operating lever for the READY-TO-EARTH function.
The left-hand control gate returns to its initial position.
The opening for the READY-TO-EARTH function is closed.
Close the circuit-breaker (see page 148, "Circuit-breaker operation").
Fig. 180: Operating the three-position disconnector for the READY-TO-EARTH function
DANGER
Danger! High voltage! The earthing process is not completed until the circuit-breaker is closed.
Close the circuit-breaker after having switched the three-position disconnector to READY-
TO-EARTH position.