EasyManua.ls Logo

Siemens 8DB10 - Page 174

Siemens 8DB10
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
174/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Fig. 203: Bus sectionalizer (system 2 described, system 1 applies accordingly)
Switching operation Switching operation is only possible if Type
Q2 CLOSED/OPEN Q02 OPEN, Q25 OPEN mechanical
Q20 CLOSED/OPEN Q02 OPEN, Q205 OPEN electromechanically / mechanically
Q25 CLOSED/OPEN Q02 OPEN, Q2 OPEN mechanical
Q205 CLOSED/OPEN Q02 OPEN, Q20 OPEN electromechanically / mechanically
Q02 CLOSED (mechanically)
Q02 CLOSED (electrically) Q2, Q20, Q25, as well as Q205 not in
intermediate position
electrical
Q02 OPEN (electrically) - being released by a bus coupler lock-in - it is not
interlocked by a locking device when the busbar
system is earthed
electrically / mechanically
Q02 OPEN (mechanically) it is not interlocked by a locking device when the
busbar system is earthed
mechanical
Additionally, electromechanical interlocks may be fitted for disconnectors and earthing switches or for earthing switches.
Fig. 204: Top-mounted bus sectionalizer (system 2 described, system 1 applies accordingly)
Switching operation Switching operation is only possible if Type
Q21 CLOSED/OPEN Q215 OPEN mechanical
Q22 CLOSED/OPEN Q225 OPEN mechanical
Q215 CLOSED/OPEN Q21 OPEN mechanical
Q225 CLOSED/OPEN Q22 OPEN mechanical
Additionally, electromechanical interlocks may be fitted for disconnectors and earthing switches or for earthing switches.
Fig. 205: Disconnectable busbar connection
Switching operation Switching operation is only possible if Type
Q61 or Q62 CLOSED/OPEN permitted by internal or external switchgear
interlocks, Q81 or Q82 OPEN
electromechanical / mechanical
Q81 or Q82 CLOSED/OPEN permitted by internal or external switchgear
interlocks, Q61 or Q62 OPEN
electromechanical / mechanical
Additionally, electromechanical interlocks may be fitted for disconnectors and earthing switches or for earthing switches.

Table of Contents