864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 35/214
Description
VOIS+, VOIS R+
Fig. 19: Voltage indicator type VOIS+
Features of
VOIS+, VOIS R+
Integrated display, without auxiliary power
With indication "A1" to "A3" (see page 177, "Indications VOIS, VOIS R+, CAPDIS -S1+/-S2+")
Maintenance-free, repeat test required
With integrated 3-phase test socket for phase comparison
(also suitable for plug-in voltage indicator)
Degree of protection IP 54, temperature range -25 °C to +55°C
With integrated signaling relays (only VOIS R+)
"M1": Operating voltage present at one phase L1, L2 or L3 as a minimum
"M2": Operating voltage not present at L1, L2 and L3
CAPDIS-S1+/S2+
Fig. 20: Voltage indicator type CAPDIS-S2+ (option)
Common features of
CAPDIS -S1+/-S2+
Maintenance-free
Integrated display, without auxiliary power
Integrated repeat test of the interfaces (self-monitoring)
With integrated function test (without auxiliary power) by pressing the "Test" button
Adjustable to different operating voltage ranges
With integrated 3-phase test socket for phase comparison
(also suitable for plug-in voltage indicator)
Degree of protection IP 54, temperature range –25 °C to +55 °C
With signal-lead test
With overvoltage monitoring and signaling at 1.2 times operating voltage