864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 51/214
Installation
Room dimensions and
wall distances
Load-bearing capacity
of the floor
Fig. 36: Wall-standing arrangement
Fig. 37: Free-standing arrangement
* Depending on national requirements
** Lateral wall distance ≥ 500 mm optionally required on the left or on the right
*** Lateral minimum wall distance ≥ 100 mm optionally possible on the left
or on the right
Load data and minimum distances
Constant loads Vertical single load 12 kN ****)
Not constant loads Live load
9 kN/m
2
Minimum distances Control aisle 800 mm *)
Minimum lateral wall distance 100 mm **)
Lateral wall distance 500 mm ***)
Ceiling height 2900 mm
Minimum door opening Height 2700 mm ****)
Width 900 / 1900 mm *****)
*) Depending on national requirements.
**) Optionally possible on the left or on the right.
***) Optionally required on the left or on the right.
****) Without busbar components / height of low-voltage compartment 850 mm
*****) Individual panel without transport packing
(for group deliveries and bringing in with transport packing, see page 57, "Transport units "