EasyManua.ls Logo

Siemens 8DB10 - Page 55

Siemens 8DB10
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 55/214
Installation
Siemens recommendation for the floor fixing
Fig. 46: Screwed floor fixing
Upper edge of finished floor
Floor fixing plate (holder for profiles at a distance
1200 mm), see page 56, "Floor fixing plate"
C-profile CB 50 x 30, EN 10025, S235JR
Hook-head bolt M16x35-4.6
Washer R18, DIN 440/ISO 7094, S235JRG2C + L
Hexagonal nut M16-8, DIN EN ISO 4032
Base frame of the switchgear
Min. 50 mm
Min. 90 mm
80 mm
Raw floor
Expansion dowel with hexagonal bolt and washer,
FAN 12/10
Floor finish
Fig. 47: Welded floor fixing
Upper edge of finished floor
Base frame of the switchgear
Welding in fixing opening of base frame
U-profile U80, DIN 1026
Floor fixing plate (holder for profiles at a distance
1200 mm), see page 56, "Floor fixing plate"
Min. 55 mm
Min. 90 mm
80 mm
Raw floor
Expansion dowel with hexagonal bolt and washer,
FAN 12/10
Floor finish
Fig. 48: Fixing on double floor
Upper edge of double floor
Hexagonal bolt M10-8, DIN 931/933
Washer 10.5-St, EN ISO 7093-1
Hexagonal nut M10-8, DIN EN ISO 4032
Base frame of the switchgear
Substructure
Supporting profile (e.g. profile 70 x 40 x 2)
Floor plate (approx. 36 mm thick)