Installation
60/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
If the comprehensive accessories, the delivered switchgear or parts thereof have to be stored
before installation, a suitable storage room or place has to be selected and prepared.
Intermediate storage of the transport units:
In original packing as far as possible
Observe the permissible storage temperature from -25° C to +70° C in accordance with
the installed secondary devices. In the individual case, the electronic components must be
checked regarding the permissible limit temperature and the relevant temperatures for
the application.
In a weatherproof place
Protected against damage
Store transport units in such a way that they can be taken out later in the correct order
for installation.
Storage in closed rooms The following switchgear parts must be stored in closed rooms:
Unpacked parts
Transport units which are not packed in seaworthy crates
The storage room must have the following characteristics:
Well-ventilated
Free of dust
Dry and protected against flooding
Relative humidity should not exceed 50%
Protected against vermin (e.g., insects, mice, rats)
Even floor to enable stable storage
Floor with adequate load-bearing capacity
Sufficient size to enable clearly arranged storage
Do not unpack small parts to avoid corrosion and loss.
Store transport units in such a way that they can be taken out later in the correct order for
installation.
Provide for sufficient ventilation in heated storage rooms.
Check transport units for condensation every 4 weeks.
If the inside of the packing or parts of the switchgear show condensation:
Remove the packing, dry the switchgear and the packing. Refit the packing.
Outdoor storage The storage place must have the following characteristics:
Protected against rain water
Protected against flooding as well as melting water from snow and ice
Protected against pollution and vermin (e.g., insects, mice, rats)
Even floor to enable stable storage
Floor with adequate load-bearing capacity
Sufficient size to enable clearly arranged storage
Place transport units on planks or square timber for protection against floor humidity.
Store transport units in such a way that they can be taken out later in the correct order for
installation.
After 6 months (12 months with seaworthy long-time packing) of storage, unpack the
transport units and store them in closed rooms, or regenerate the seaworthy packing
(see below).