864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 73/214
Installation
In these cases, the busbar joints are not accessible anymore after the transport units have
been interconnected.
For this reason, the busbar sections must be re-assembled from the panel on the left of the
panel joint to the panel on the right before starting the assembly. The illustration below
shows the final position after re-assembling.
Clear the assembly opening : Remove all horizontal flange covers on the busbar housings
of the panel located on the left of the panel joint.
Undo the busbar sections ⑤ at the joints ③ in the busbar housing through the assembly
opening ② . The busbar supports ⑨ remain on the disassembled busbar sections.
Take the busbar sections ⑤ out of the housings together with the associated busbar
supports ⑨ through the vertical flange ④ .
Mount the busbar sections at the joints in the busbar housings of the panel located on
the right of the panel joint. Assembly takes place through the vertical flanges ⑧ .
Check alignment and parallel position of the assembled busbar sections and correct
if required.
Fig. 64: Re-assembling the busbars (example with elbow coupling)
Fig. 65: Re-assembling the busbars (example with flexible connectors)
Busbar housing of the panel located on the left
of the panel joint
Busbar housing of the panel located on the
right of the panel joint
Assembly openings (horizontal flanges)
Joints of the panel located on the right of the
panel joint
Joints of the panel located on the left of the
panel joint
Vertical flanges of the panel located on the
right of the panel joint
Vertical flanges of the panel located on the left
of the panel joint
Elbow coupling
Busbar sections
Flexible connectors
Busbar support

Table of Contents