Installation
76/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
For flange connections with compensator, insulating sleeves must be inserted at
the bolted joints.
Flange connections with insulating joint: Push insulating ring between the flanges.
Fasten M8x45 bolts crosswise with one insulating sleeve each. Tightening torque: 20 Nm.
If there are e. g. busbar current transformers or expansion joints available,
the flange connections must be equipped with insulating sleeves.
Fig. 69: Flange connection with
compensator and insulating sleeve
Insulating sleeve
Busbar housing
Insulating ring (thickness: 18 mm)
Toroidal sealing rings
Compensator
Fig. 70: Long busbar housing with insulating joint
Busbar housing
Toroidal sealing ring
Insulating ring (thickness: 4 mm)
with sealing ring
Fig. 71: Flange connections with
insulating sleeve
Current transformer mounting plate
Flange
Insulating ring
Compensator
Insulating sleeve

Table of Contents