AddFEM
Commissioning / Operation / Maintenance
5-47
AddFEM
C79000–G8076–C900–03
Start–up Characteristics
During an initial start–up or restart the logical address of the inputs and outputs
and the diagnostic address are formed from the geographic AddFEM address.
The range limits (AIx_HRG and AIx_LRG) are converted into factors and offsets in
order to calculate the current input values. In case of incorrect error configuration,
for example Upper limit <= Lower limit the input value is set to ”zero.
During start–up a factor for calculating the speed (rpm) is calculated for each coun-
ter value. The number of pulses per revolution (number of teeth) has to be configu-
red at the Cox_NUM input parameters.
Time Response
Does not exist.
Message Characteristics
The block does not have message characteristics.
Operator Control and Monitoring
The block does not have a faceplate.
Parameters