Technical Data AddFEM
4-28
AddFEM
C79000–G8076–C900–03
Information in the Diagnostic Message:
Set error state 1
Unset error state 0
Group status (byte 9, 10) Group display – Combination by ORing individual errors
AI status (byte 11, 12) Individual status of the analog inputs
AO status (byte 13, 14) Individual status of the analog outputs
BO/BI status (byte 15, 16) Individual status of the combined binary outputs and outputs
Internal error (byte 17, 18) Individual status of the internal error messages
Individual
signal
Forms the
group dis-
play
Description
BUS
1)
Corresponding to BUSF (... at S7) display of PROFIBUS DP errors
INT Corresponding to INTF display of internal errors
EXT Corresponding to EXTF display of external faults (channel faults)
– ORing of AIF, AOF, BOF, etc.
AIF EXT Group error analog inputs – ORing of AI_1F to AI_12F
AOF EXT Group error analog outputs – ORing of A0_1F to AO_8F
BOF EXT Group error binary outputs – ORing of DO_1F to DO_16F
BSV BAR 1 External supply voltage DO 1 ... 8 missing
BSV BAR 2 External supply voltage DO 9 ... 16 missing
AI_1F..AI_12F AIF Individual error / qualifier of the analog inputs – are set or reset directly
by the acquisition part.
AO_1F..AO_8F AOF Individual error / qualifier of the analog outputs (see above)
BO_1F..BO_12
F
BOF Individual error / qualifier of the binary outputs (see above)
S1_MRES
2)
INT Key switch in position MRES
S1_STOP
2)
INT Key switch in position STOP
S1_RUN INT Key switch in position RUN
S1_RUN_P
2)
INT Key switch in position RUN P
S2_TAST
3)
INT Slide switch in jogging position (Position 0)
S2_RAST
3)
INT Slide switch in notched position (Position 2)
CP_F INT Co–processor fault occurred
SV_P24V INT Monitoring of the external supply voltage +24 V has been triggered
SV_P15V INT Monitoring of the internal supply voltage +15 V has been triggered
SV_N15V INT Monitoring of the internal supply voltage –15 V has been triggered
SV_P20V INT Monitoring of the internal supply voltage +20 V has been triggered
SV_N20V INT Monitoring of the internal supply voltage –20 V has been triggered
RSS_F INT Fault at the optical fiber redundancy interface
RAM_F INT Check sum correction factors in the RAM invalidated