Commissioning (software)
5.7 Commissioning modes
Control Units CU240S
5-58 Operating Instructions, 11/2006, A5E00766042B AA
Automatic download fault
If the automatic download process fails, the CU will return to the parameter set previously
held in the EEPROM and the following fault codes are generated:
Table 5-17 Automatic download fault codes
Fault code Description
F0061 Automatic download of parameters was not successful.
F0063 Automatic download of parameters was not successful (e.g. wrong CU).
In this case check, whether the MMC is defective or a parameter set clone00.bin is available
or the parameter set is valid.
A valid parameter set means, it is not from a different type (eg. CU20S DP and CU240S or
failsafe and standard CUs)