Commissioning (software)
5.2 Parameters
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
5-9
Note
Parameter values that are changed using STARTER or a higher-level control do not have to
be acknowledged.
Quick commissioning
This parameter attribute identifies as to whether the parameter is included in the quick
commissioning (QC) (P0010 = 1).
Table 5-8 Parameter attributes - Quick commissioning
QC Description
No The parameter is not included in the quick commissioning
Yes The parameter is included in the quick commissioning
Value range
The value range, which is specified as a result of the data type, is restricted by the minimum
and maximum values (min, max) and using the inverter/motor quantities. Straightforward
commissioning is guaranteed in so much that the parameters have a default value. These
values (min, max, def) are so permanently saved in the inverter and cannot be changed by
the user.
Table 5-9 Parameter attributes - Value range
Value range Description
- No value entered (e.g.: "r parameter")
Min Minimum value
Max Maximum value
Def Default value
Data sets
A detailed description for the data sets is given in the respective section
Table 5-10 Data sets
BICO Description
CDS Command data set
DDS Drive data set