Commissioning (software)
5.9 Commissioning with PROFIBUS DP
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
5-103
Information about the parameter request:
Request_reference:
The value is selected at random from the valid value range. The request reference
establishes the relationship between request and response.
Request_ID:
0x01 --> This identifier is required for a read request.
Drive_object_ID:
0x00 -> Device-Representative.
No_of_parameters:
0x02 --> Two parameters are read.
Attribute_parameter_01:
0x10 --> The parameter values are read.
No_of_elements_01:
0x08 --> The current fault incident with 8 faults is to be read.
Parameter_number_01:
03B3 --> P0947 (last fault code) is read.
Subindex_01:
0x00 --> Read access starts at index 0
Attribute_parameter_02:
0x10 --> The parameter values are read.
No_of_elements_02:
0x08 --> The current fault incident with 8 faults is to be read.
Parameter_number_02:
03B5 --> P0949 (last fault code) is read.
Subindex_02:
0x00 --> Read access starts at index 0.
1. Create a response data block e.g. DB2 for the response