Functions
8.5 Analog inputs (A/D converter)
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
8-19
Depending on the AI type or source, the appropriate connection must be made. Using, as an
example, the internal 10 V voltage source, a connection is shown in the figure below.
$
'
./9
./9
./$,
./$,
!N˖
$
'
./9
./9
./$,
./$,
$
'
./$,
./$,
$
'
./$,
./$,
P$
Figure 8-12 Example of a connection for AI voltage and current input
The AI channel has several function units (filter, scaling, dead zone, see figure below).
./
./
$
'
3
3
3
3
U 3[[[[
U
3
$,
$,
U
U
U;
3
3
3
$,
W\SH
$,
W\SH
',3VZLWFK
$,
VFDOLQJ
$,
GHDG]RQH
)XQFWLRQ
Figure 8-13 AI channel
Note
When the filter time constant P0753 (AI-PT1) is increased, this smooths the AI input signal
therefore reducing the ripple. When this function is used within a control loop, this smoothing
has a negative impact on the control behavior and immunity to noise (the dynamic
performance deteriorates).
Note
The analog inputs can be used as digital inputs. Setting P0712 and P0713 > 0 assign digital
input functions to the analog inputs.