EasyManua.ls Logo

Siemens CU240S DP-F - Page 367

Siemens CU240S DP-F
410 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
8.24 Open-loop and closed-loop control
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
8-171
In the steady-state condition, the field-generating current component id is proportional to the
flux Φ and the torque is proportional to the product of i
d
and i
q
.
M ~ Φ * i
q
Φ ~ i
d,stat
M ~ i
d
* i
q
When compared to V/f control, Vector control has the following advantages:
Stable during load and setpoint changes
Short rise times for setpoint changes (→ better control performance)
Short rise times for load changes (→ better noise/disturbance characteristics)
Accelerating and braking are possible with a max. adjustable torque
The motor and motor machine are protected using the adjustable torque limit, both when
motoring and regenerating
The motor and braking torque are controlled independently of the speed
Full holding torque is possible at 0 speed.
These advantages are, under certain circumstances, already achieved without using speed
feedback.
The Vector control can be used both with and without speed encoder.
The following criteria provide a basis as to when a speed actual value encoder is required:
High speed accuracy is required
High requirements are placed on the dynamic response
Improved control performance
Improved immunity to disturbances.
The torque is to be controlled over a control range greater than 1:10
A defined and/or a changing torque has to be maintained for speeds below approx. 10 %
of the rated motor frequency P0310.
When it comes to entering a setpoint, the Vector control (see table below) is sub-divided into:
Closed-loop speed control, and
Closed-loop torque/current control (known as: Closed-loop torque control).
Table 8-35 Vector control versions
Vector control (closed-loop) Without encoder With encoder
Closed-loop speed control P1300 = 20 and P1501 = 0 P1300 = 21 and P1501 = 0
P1300 = 22 or P1300 = 23 or Closed-loop torque control
P1300 = 20 and P1501 = 1 P1300 = 21 and P1501 = 1
When closed-loop speed control is used, the closed-loop torque control is secondary. This
type of cascaded closed-loop control has proven itself in practice regarding commissioning
and increased transparency.

Table of Contents

Other manuals for Siemens CU240S DP-F

Related product manuals