EasyManuals Logo

Siemens CU240S DP-F User Manual

Siemens CU240S DP-F
410 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
Installing/Mounting
4.3 Connecting a CU240S DP or CU240S DP-F via PROFIBUS DP
Control Units CU240S
4-16 Operating Instructions, 11/2006, A5E00766042B AA
Equipotential bonding
Differences in potential (for example, due to different mains supplies) between the inverters
and the PROFIBUS DP master must be avoided.
Recommended equipotential bonding cables:
16 mm
2
Cu for equipotential bonding cables up to 200 m long
25 mm
2
Cu for equipotential bonding cables of over 200 m long.
Equipotential bonding cables must be routed as close as possible to signal leads; this
means that the area between the bonding conductor and signal lead is as small as
possible.
Equipotential bonding cables must be contacted in a 360° connection with the earth
electrode/PE conductor.

Table of Contents

Other manuals for Siemens CU240S DP-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240S DP-F and is the answer not in the manual?

Siemens CU240S DP-F Specifications

General IconGeneral
BrandSiemens
ModelCU240S DP-F
CategoryControl Unit
LanguageEnglish

Related product manuals