Commissioning (software)
5.6 Parameterization with STARTER
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
5-17
Note
Via P0014 the store mode can be changed,
P0014 = 0: parameter changes stored in RAM (default)
P0014 = 1: parameter changes stored in EEPROM
Parameter sets that have been changed offline can be transferred to the inverter using the
download
button.
Caution
Parameters for fail-safe functions can only be changed in the online mode.
When downloading parameters via STARTER, parameters belonging to fail-safe functions
will not be downloaded.