Commissioning (software)
5.7 Commissioning modes
Control Units CU240S
5-34 Operating Instructions, 11/2006, A5E00766042B AA
Selection of command source
The available command sources depend on the used CU.
Default setting on the control unit used the command source is set per default to different
values.
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0700 = 2/6 Selection of command source
This selects the digital command source
0: Factory default setting
1: OP (keypad)
2: Terminal (P0701 … P0709), factory setting for CU240S
4: USS on RS232
5: USS on RS485 (not available with CU240S DP and CU240S DP-F)
6: Fieldbus (P2050 … P02091), factory setting for CU240S DP and CU240S DP-F, not
available with CU240S)