EasyManua.ls Logo

Siemens CU240S DP-F - Page 92

Siemens CU240S DP-F
410 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning (software)
5.7 Commissioning modes
Control Units CU240S
5-36 Operating Instructions, 11/2006, A5E00766042B AA
Assigning digital output functions
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P0731 = 52:3 BI: function of digital output 0 (DO0), defines the source for digital output 0
Terminal 18: DO0, NC/Terminal 19: DO0, NO/Terminal 20: DO0, COM
52:3 Inverter fault active
P0732 = 52:7 BI: function of digital output 1,defines the source for digital output 1
Terminal 21: DO1, NO/Terminal 22: DO1, COM
52:7 Inverter warning active
P0733 = 0:0 BI: function of digital output 2, defines the source for digital output 2
Terminal 23: DO0, NC/Terminal 24: DO0, NO/Terminal 25: DO0, COM
0:0 Digital output disabled
P0748 Invert digital outputs
Bits 0, 1 and 2 can be used to invert the signals of digital outputs 0, 1 and 2
Frequency setpoint set
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1000 = ? Selection of frequency setpoint
0: No main setpoint
1: MOP setpoint (P1031 … P1040)
2: Analog setpoint (P0756 … P0762), factory setting for CU240S
3: Fixed frequency (P1001 … P1023)
6: Fieldbus (P2050 … P02091), factory setting for CU240S DP and CU240S DP-F, not
available with CU240S)
7: Analog setpoint 2
10: Additional setpoint (1 = MOP) + Main setpoint (0 = No main setpoint)
11: Additional setpoint (1 = MOP) + Main setpoint (1 = MOP)
12: Additional setpoint (1 = MOP) + Main setpoint (2 = Analog setpoint)
62: Additional setpoint (6 = Fieldbus) + Main setpoint (2 = Analog setpoint)
63: Additional setpoint (6 = Fieldbus) + Main setpoint (3 = Fixed frequency)
Frequency setpoint via MOP (P1000 = 1)
Parameter Description (Parameter name and factory setting (if not variable) in bold) Setting
P1031 = 0 Setpoint memory of the MOP
The last motorized potentiomenter setpoint, which was active before the OFF command or
switching-off, can be saved.
0: MOP setpoint will not be stored
1: MOP setpoint will be stored in P1040
P1032 = 1 Inhibit reverse direction of MOP
0: reverse direction is allowed
1: Reverse direction inhibited
P1040 = 5 Setpoint of the MOP
Defines the setpoint [Hz] of the motorized potentiometer (MOP).

Table of Contents

Other manuals for Siemens CU240S DP-F

Related product manuals