Communications configuring
3-108 System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
Rules:
The communications reference is as required within the framework of
the general rules.
Local LSAP must be the same as the "Remote LSAP" of the remote
client.
The remote address and remote LSAP can be entered, defined, but
then only the appropriately selected client can establish a connection
(access protection!); or both values can be set to 255, and then the
association is open for all.
Max. PDU length should only be changed, if a remote client cannot
handle the specified length.
The monitoring interval must coincide with the remote client.
The Read, Write, Get OV(detailed version) utilities and symbolic
addressing are always supported from SIMADYN D servers as
responder (".ind"). The information report utility is not required.
The maximum number of parallel "Receive" tasks must be set at least
as high as the maximum number of "Transmit" tasks of the partner.
Features:
Non-cyclic data transfer
SIMADYN D is exclusively a client.
A connection (minimum) must be configured for each remote server.
SIMADYN D establishes the connection and initiates data transfer.
The objects, which SIMADYN D accesses in the remote server, are
defined by the CFC configuring (address stage 2 at the address I/O).
Several utilities can run in parallel
Application:
All SIMADYN D utilities, where SIMADYN D is a client.
Non-cyclic client