Pulse repetition
Pulse repetition is calculated as follows:
)&
$PRXQWSHUSXOVH
3XOVHUHSHWLWLRQ
0HDVXUHGIORZUDWH
Note
Pulse width must be selected with the view that remaining time is always greater than pulse
width at the highest measured flow.
Example
Pulse output configuration (channels 2 to 4)
Operation mode = Pulse output
Process value = Mass flow
Amount = 1 kg
Pulse width = 1 ms
Measured mass flow value = 10 kg/s (constant)
Result:
Pulse repetition = 100 ms
Output frequency = 10 pulses per second with a pulse width of 1 ms
Remaining time between pulses is 99 ms
8.6.3 Frequency output
The frequency output function supplies a frequency (50% duty cycle) proportional to the
selected process value.
Frequency is calculated as follows:
)&
0HDVXUHGPDVVIORZYDOXH
)UHTXHQF\
)ORZ9DOXH+LJK)ORZ9DOXH/RZ
;
)UHTXHQF\9DOXH+LJK)UHTXHQF\9DOXH/RZ
Example
This example shows how to calculate the output frequency for any measured flowrate:
Frequency output configuration:
Operation Mode = Frequency Output (Channel 2 to 4)
Process Value = Massflow