Description Specification
Installation environment Industrial including chemical processing plants
Insulation material PVC
Halogen-free Yes
RoHS compliant Yes
Permissible temperature range [°C (°F)] -20 to +105
Table 11-24 Cable glands and entries
Description Specification
Glands
● Material
– Nylon
1)
– Brass/Ni plated
– Stainless steel AISI 316/1.4404
● Cable cross section
– ∅ 5 to 10 mm (0.20" to 0.39")
Entry
● 1 x M20 or 1 X NPT ½" for communication
1)
: If operating temperature is below -20 °C (-4 °F), use Brass/Ni plated or stainless steel cable
glands.
Note
Ex installation
Glands must be Ex-d certified.
11.7 Operating conditions
11.7.1 Rated operating conditions
Table 11-25 Basic conditions
Description Specification
Ambient temperature (°C[°F])
(Humidity max. 90 %)
Operation:
Transmitter without display
Transmitter with display
-40 to +60 [-40 to +140]
-20 to +60 [-4 to +140]*
Ambient temperature (°C[°F])
(Humidity max. 90 %)
Storage:
Transmitter without display
Transmitter with display
-40 to +70 [-40 to +158]
-40 to +70 [-40 to +158]
Climate class DIN 60721-3-4
Altitude Up to 2000 m (6560 ft)
Technical data
11.7 Operating conditions
MASS 2100 & FC300 (FCT030)
234 Operating Instructions, 06/2017, A5E39789040-AA