EasyManua.ls Logo

Siemens FC300 - Operating Conditions; Rated Operating Conditions

Siemens FC300
518 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description Specification
Installation environment Industrial including chemical processing plants
Insulation material PVC
Halogen-free Yes
RoHS compliant Yes
Permissible temperature range [°C (°F)] -20 to +105
Table 11-24 Cable glands and entries
Description Specification
Glands
Material
Nylon
1)
Brass/Ni plated
Stainless steel AISI 316/1.4404
Cable cross section
∅ 5 to 10 mm (0.20" to 0.39")
Entry
1 x M20 or 1 X NPT ½" for communication
1)
: If operating temperature is below -20 °C (-4 °F), use Brass/Ni plated or stainless steel cable
glands.
Note
Ex installation
Glands must be Ex-d certified.
11.7 Operating conditions
11.7.1 Rated operating conditions
Table 11-25 Basic conditions
Description Specification
Ambient temperature (°C[°F])
(Humidity max. 90 %)
Operation:
Transmitter without display
Transmitter with display
-40 to +60 [-40 to +140]
-20 to +60 [-4 to +140]*
Ambient temperature (°C[°F])
(Humidity max. 90 %)
Storage:
Transmitter without display
Transmitter with display
-40 to +70 [-40 to +158]
-40 to +70 [-40 to +158]
Climate class DIN 60721-3-4
Altitude Up to 2000 m (6560 ft)
Technical data
11.7 Operating conditions
MASS 2100 & FC300 (FCT030)
234 Operating Instructions, 06/2017, A5E39789040-AA

Table of Contents

Related product manuals