Default settings
B
The following tables show the default settings as well as the range for various parameters.
The parameters can be accessed on three levels.
Read Only
Allows no configuration. The user is only able to view the parameter values. No PIN code
required.
User
Allows configuration and service of all parameters except calibration parameters. Default
PIN code is 2457.
Expert
Allows configuration and service of all parameters including flow and density calibration
parameters. Default PIN code is 2834.
B.1 Sensor
Table B-1 Sensor
HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.1.1 Flow Direction Select pos/neg flow. Default pos
flow is indicated by arrow on sen‐
sor.
Positive
Negative
Positive
User
2.1.2 Process Noise Damping Select process noise damping
level.
* 1: Low … 5: High
Duplex pump (3)
Centrifugal
pump (1:low)
Triplex pump
(2)
Duplex pump
(3)
Simplex pump
(4)
Cam pump (5)
high
User
2.1.3 Zero point adjustment
2.1.3.1 Select Zero Point Adj. Selected zero-point adjustment
method. Automatic zero point
adjustment is recommended.
Auto
Auto
Manual
2.1.3.2 Zero Point Adjustment Wizard
2.1.3.3 Duration Define zero-point adjustment du‐
ration.
30
[s]
1 to 999 User
MASS 2100 & FC300 (FCT030)