Bidirectional flow with symmetrical scaling
)&
v
v
mA
Kg/h
v
v
v
v
v
P$
P$
P$
P$
P$
NJKNJKNJKNJK
Upper scaling
Lower scaling
Low-flow cut-off
Upper alarm value
Maximum measurement value
Upper range
Lower range
Minimum measurement value
Measurement range
Current output setting
Process value = Massflow
Direction = Bidirectional (Symmetric)
Current Mode = 4-20 mA NAMUR
Upper Scaling = 400 kg/h
Lower Scaling = 100 kg/h
Fail Safe Mode = Maximum current
Low-Flow Cut-Off = 25 kg/h
8.6.2 Pulse output
The pulse output function supplies pulses equivalent to a configured amount of accumulated
volume or mass. The pulse width is configured and the pulse repetition is proportional to the
selected flow rate.
Functions
8.6 Inputs and outputs
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 149